**For power de-rating from 50°C to 80°C, see power de-rating on page 3.
***PARD is measured with an AC coupling mode, 5cm wires, and in parallel with 0.1?F ceramic capacitor & 47?F electrolytic capacitor.
Mechanical
Case Cover / Chassis: Aluminium
Dimensions (L x W x D): 121 x 85 x 124.1 mm (4.76 x 3.35 x 4.86 inch)
Unit Weight: 0.96 kg (2.12 lb)
Indicator: Green LED--> DC OK
Cooling System: Convection
Terminal:
Input 3 Pins (Rated 300V/15A)
Output 4 Pins (Rated 300V/15A)
Wire: Input / Output AWG 18-12
Mounting Rail: Standard TS35 DIN Rail in accordance with EN 60715
Noise (1 Meter from power supply): Sound Pressure Level (SPL) < 40dBA
Environment
Surrounding Air Temperature:
Operating -25°C to +80°C (Cold Start at -40°C)
Storage -40°C to +85°C
Power De-rating:
Vertical Mounting > 50°C de-rate power by 2.5% / °C
Horizontal Mounting > 40°C de-rate power by 2.5% / °C
Operating Humidity: 5 to 95% RH (Non-Condensing)
Operating Altitude: 0 to 2,500 Meters (8,200 ft.)
Shock Test: Non-Operating IEC 60068-2-27, 30G (300m/S²) for a duration of 18ms, 1 time per direction, 2 times in total
Vibration: Non-Operating IEC 60068-2-6, 10Hz to 500Hz @ 30m/S² (3G peak); displacement of 0.35mm; 60 min per axis for all X, Y, Z direction
Bump Test: Operating: IEC 60068-2-29, Half Sine Wave: 10G for a duration of 11ms,1,000 times per direction, 6,000 times in total
Over Voltage Category: III According to IEC/EN 62477-1 / EN 60204-1 (clearance and creepage distances) and IEC 62103 (safety part)
Pollution Degree: 2
Protections
Overvoltage:
< 57V, SELV Output, Hiccup Mode,
Non-Latching (Auto-Recovery)
Overload / Overcurrent:
> 150% of rated load current, Hiccup Mode,
Non-Latching (Auto-Recovery)
Over Temperature:
< 80°C Surrounding Air Temperature @ 100% load,
Non-Latching (Auto-Recovery)
Short Circuit:
Hiccup Mode, Non-Latching
(Auto-Recovery when the fault is removed)
Internal Fuse at L pin: T6.3AH
Degree of Protection: IP20
Protection Against Shock: Class I with PE* connection
*PE: Primary Earth
Reliability Data
MTBF:
> 500,000 hrs. as per Telcordia SR-332
I/P: 115Vac & 230Vac, O/P: 100% load, Ta: 25°C
Expected Cap Life Time: 10 years (115Vac & 230Vac, 50% load @ 40°C)
Safety Standards / Directives
Electrical Equipment of Machines: EN 60204-1 (over voltage category III)
Electrical Equipment for Use in Electrical Power Installations: IEC/EN 62477-1 / IEC 62103
Safety Entry Low Voltage: PELV* (EN 60204-1), SELV (EN 60950-1)
Overvoltage on Telecommunication Networks: TNV-1 circuit
Electrical Safety:
SIQ Bauart: EN 60950-1, EN 62368-1
UL/cUL recognized:
UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395)
UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E191395)
CB scheme: IEC 60950-1, IEC 62368-1
Industrial Control Equipment:
UL/cUL listed: UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355)
CSA: CSA C22.2 No. 107.1-01 (File No. 181564)
Hazardous Location / ATEX (For DRP048V240W1BA):
cCSAus: CSA C22.2 No. 213-M1987 and ANSI / ISA 12.12.01
[Class I, Division 2, Group A, B, C, D T4, Ta= -25°C to +80°C (Vertical: > +50°C derating, Horizontal: > +40°C derating)]
ATEX: EN 60079-0, EN 60079-15 [ II 3G Ex nA nC IIC T4 Gc, Ta= -25°C to +80°C
(Vertical: > +50°C derating, Horizontal: > +40°C derating)] Certificate No. EPS 12 ATEX 1 491 X
CE: In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
For DRP048V240W1BA: In conformance with Equipment for explosive atmospheres (ATEX) directive 2014/34/EU
Galvanic Isolation:
Input to Output 4.0KVac
Input to Ground 1.5KVac
Output to Ground 1.5KVac
*Output must be earthed in the final unit in order to comply with PELV requirements according to standard EN 60204-1.
EMC
Emissions (CE & RE):
Generic Standards: CISPR 32, EN 55032, CISPR 11,
EN 55011, FCC Title 47: Class B
Component Power Supply for General Use: EN 61204-3
Immunity: Generic Standards: EN 55024, EN 61000-6-1, EN 61000-6-2
Power Frequency Magnetic Fields: IEC 61000-4-8 Criteria A1) 30A/Meter
Voltage Dips and Interruptions: IEC 61000-4-11 100% dip; 1 cycle (20ms); Self Recoverable
Low Energy Pulse Test (Ring Wave):
IEC 61000-4-12 Level 3 Criteria A1)
Common Mode2): 2kV
Differential Mode3): 1kV
Harmonic Current Emission: IEC/EN 61000-3-2, Class A
Voltage Fluctuation and Flicke:r IEC/EN 61000-3-3
1) Criteria A: Normal performance within the specification limits
2) Asymmetrical: Common mode (Line to earth)
3) Symmetrical: Differential mode (Line to line)